Electrical

⫶
<cim:SwitchInfo rdf:ID="ART4179"> <!-- electrical characteristics -->
    <cim:IdentifiedObject.name>8DJH 24kV</cim:IdentifiedObject.name>
    <cim:IdentifiedObject.aliasName>810:nis_el_int_switch_art</cim:IdentifiedObject.aliasName>
    <cim:IdentifiedObject.description>Gas-Insulated Medium-Voltage Switchgear</cim:IdentifiedObject.description>
    <cim:SwitchInfo.ratedVoltage>24000.0000</cim:SwitchInfo.ratedVoltage>
</cim:SwitchInfo>
<cim:Switch rdf:ID="TEI127390">
    <cim:IdentifiedObject.name>8DJH 24kV</cim:IdentifiedObject.name>
    <cim:IdentifiedObject.aliasName>276857882:nis_el_int_switch</cim:IdentifiedObject.aliasName>
    <cim:IdentifiedObject.description>Switch</cim:IdentifiedObject.description>
    <cim:ConductingEquipment.BaseVoltage rdf:resource="#BaseVoltage_16000"/> <!-- voltage -->
    <cim:PowerSystemResource.Location rdf:resource="#_location_1621079552_427087358_276857884"/>
    <cim:PowerSystemResource.PSRType rdf:resource="#PSRType_Substation"/>
    <cim:PowerSystemResource.AssetDatasheet rdf:resource="#ART4179"/> <!-- info reference -->
    <cim:Equipment.EquipmentContainer rdf:resource="#FEL215886"/>
    <cim:Switch.normalOpen>false</cim:Switch.normalOpen> <!-- state -->
</cim:Switch>
⫶
                        
Spatial

⫶
<cim:Location rdf:ID="_location_1621079552_427087358_276857884"> <!-- spatial location -->
    <cim:Location.CoordinateSystem rdf:resource="#pseudo_wgs84"/>
    <cim:Location.type>geographic</cim:Location.type>
</cim:Location>
<cim:PositionPoint rdf:ID="_location_1621079552_427087358_276857884_p"> <!-- point location -->
    <cim:PositionPoint.Location rdf:resource="#_location_1621079552_427087358_276857884"/>
    <cim:PositionPoint.sequenceNumber>0</cim:PositionPoint.sequenceNumber>
    <cim:PositionPoint.xPosition>7.22933091967</cim:PositionPoint.xPosition>
    <cim:PositionPoint.yPosition>47.1121810794</cim:PositionPoint.yPosition>
</cim:PositionPoint>
<cim:Switch rdf:ID="TEI127390">
    <cim:IdentifiedObject.name>8DJH 24kV</cim:IdentifiedObject.name>
    <cim:IdentifiedObject.aliasName>276857882:nis_el_int_switch</cim:IdentifiedObject.aliasName>
    <cim:IdentifiedObject.description>Switch</cim:IdentifiedObject.description>
    <cim:ConductingEquipment.BaseVoltage rdf:resource="#BaseVoltage_16000"/>
    <cim:PowerSystemResource.Location rdf:resource="#_location_1621079552_427087358_276857884"/>  <!-- loc. reference -->
    <cim:Switch.normalOpen>false</cim:Switch.normalOpen>
⫶
                        
Topology

⫶
<cim:Terminal rdf:ID="TEI127390_terminal_1">
    <cim:IdentifiedObject.name>TEI127390_terminal_1</cim:IdentifiedObject.name>
    <cim:ACDCTerminal.sequenceNumber>1</cim:ACDCTerminal.sequenceNumber>
    <cim:Terminal.phases rdf:resource="http://iec.ch/TC57/2013/CIM-schema-cim16#PhaseCode.ABC"/>
    <cim:Terminal.ConnectivityNode rdf:resource="#PIN518369_node"/> <!-- connectivity reference -->
    <cim:Terminal.ConductingEquipment rdf:resource="#TEI127390"/> <!-- equipment reference -->
</cim:Terminal>
⫶
<cim:ConnectivityNode rdf:ID="PIN518369_node"> <!-- connection -->
    <cim:IdentifiedObject.name>PIN518369</cim:IdentifiedObject.name>
    <cim:IdentifiedObject.aliasName>276857893:nis_el_int_pin</cim:IdentifiedObject.aliasName>
    <cim:IdentifiedObject.description>TEI127390 pin 2</cim:IdentifiedObject.description>
    <cim:ConnectivityNode.ConnectivityNodeContainer rdf:resource="#STA212"/>
</cim:ConnectivityNode>
⫶
<cim:Terminal rdf:ID="REF201114_terminal_1"> <!-- connection -->
    <cim:IdentifiedObject.name>REF201114_terminal_1</cim:IdentifiedObject.name>
    <cim:ACDCTerminal.sequenceNumber>1</cim:ACDCTerminal.sequenceNumber>
    <cim:Terminal.phases rdf:resource="http://iec.ch/TC57/2013/CIM-schema-cim16#PhaseCode.ABC"/>
    <cim:Terminal.ConnectivityNode rdf:resource="#PIN518369_node"/> <!-- connectivity reference -->
    <cim:Terminal.ConductingEquipment rdf:resource="#REF201114"/> <!-- equipment reference -->
</cim:Terminal>
⫶
                        
Asset

⫶
<cim:LifecycleDate rdf:ID=TEI127390_lifecycle"> <!-- lifecycle -->
    <cim:LifecycleDate.installationDate>2001</cim:LifecycleDate.installationDate>
</cim:LifecycleDate>
<cim:Asset rdf:ID="TEI127390_asset">
    <cim:IdentifiedObject.name>TEI127390</cim:IdentifiedObject.name>
    <cim:IdentifiedObject.aliasName>276857882:nis_el_int_switch</cim:IdentifiedObject.aliasName>
    <cim:IdentifiedObject.description>Line Switch</cim:IdentifiedObject.description>
    <cim:Asset.type>8DJH 24kV</cim:Asset.type>
    <cim:Asset.lifecycle rdf:resource="#TEI127390_lifecycle"/> <!-- lifecycle reference -->
    <cim:Asset.Location rdf:resource="#_location_1621079552_427087358_276857884"/>
    <cim:Asset.PowerSystemResources rdf:resource="#TEI127390"/> <!-- equipment reference -->
</cim:Asset>
⫶